RT INTELLIGENT ON-LINE UPS:
· True intelligent UPS with the MCU control.
· True on-line UPS. pure sine wave output.
· Using the pwer unit IGBT to make the UPS more efficiency and reliable.
· Output three phase 100% unbalanced load, operate continuously.
· Unique output short circuit protection, jump-free main switch.
electronic power
· It is safe and reliable with the isolation transformer.
· Whole protection against load, auto limitcurrent, it is conformed to the start requiremen of different load.
· DC cold start ability can provide convenient and flexible progamme for the users.
· Long standby time, it also can be connected with the generator and constitute the long standby time.
· Obtained remote control, remote control, remote survey port(standard equipment) and provide remote supervisory indicator.
· Offer ATS hot standby redundancy capability, it can constitute the 220VDC input inverter for the special use of power station.
electronic power
| SPECIFICATION |
| MODEL |
RT10 |
RT15 |
RT20 |
RT30 |
RT40 |
RT60 |
RT80 |
RT100 |
RT125 |
RT150 |
| Capacity |
10KVA |
15KVA |
20KVA |
30KVA |
40KVA |
60KVA |
80KVA |
100KVA |
125KVA |
150KVA |
| Input |
|
| Voltage |
Three phase and four wire |
| Range |
±20% |
| Frequency |
50Hz±50% |
| Output |
|
| Voltage |
Three phase and four wire 380V
380V±1%(Static state); 380V±1%(Load 0~100% change) |
| Frequency |
(The unit oscilation)
Simultaneously with line input(main power status) |
| Overload capacity |
120% Operate continuosly:125-150% 30S |
| Crest ratio |
3:1 |
| THD |
Harmonic distortion of the phase voltage main wave<3%(100% Linear load) |
| Wave form |
Pure sine wave |
| 100% Unbalanced load |
Operate continuosly |
| Power factor |
0.8-1 Lagging |
| Efficiency |
>90% |
| Transfer Time |
Commercial power bypass Inverter 0ms; Inverter Commercial power<1ms |
| Short circuit |
Output shut, Not change to bypass |
| Battery |
|
| Battery Voltage |
192VCD 220VDC
(Specialuse use of power station) |
192VDC/384VDC 220VDC
(Specialuse use of power station) |
| Floating-charge Voltage |
220VDC |
220VDC/440VDC |
| End voltage |
170VDC |
170VDC/340VDC |
| Recharing Current |
6-50 ADC |
| Communication Between Human And Machine |
| LCD |
Big screen dot-maxtrix display operating staus, voltage, current, parameter, model, set etc. |
| LED |
Procedure display double route input, rectifier, inverter, battery, bypass output, static state switch, fault |
| Port |
| Communication Port |
True RS-232 port |
| Remote control and remote survey |
Remote turn on and turn off; Working status |
| A.T.S Port |
24VDC |
| Enviroment |
|
| Audible Noise |
<55dB |
<60dB |
| Working Temperature |
0~40oC |
| Relative Humidity |
90% |
| Protecting Standard |
Ip21 |
| Color |
Light grey |
| Physical |
|
| WxDxH(mm) |
410x850x1150 |
800x750x1620 |
800x750x1850 |
700x19000x1800 |
| Net Weight(KG) |
220 |
235 |
255 |
450 |
500 |
540 |
800 |
1100 |
1700 |
1800 |
|